Two-phase distribution boards
Organized two-phase feed connections for compatible modular protective devices using M5.5 contacts.
M5.5 pin-type two-phase busbars for compatible modular protective devices and OEM panel assemblies.
01 / PRODUCT VIEWThe M5.5 two-phase range uses a 17.8 mm device distance with 5.5 mm-wide, 11.5 mm-long pin contacts. The published configurations cover 210, 1000 and 1016 mm lengths, 12, 54 and 56 modules, 8–16 mm² cross-sections at 50–80 A, plus a 25 mm² / 100 A option with 6 mm pin width. The drawing shows the repeating L1 and L2/N sequence.
Choose the required conductor cross-section, finished length and module count. Dimensions B, C, D and F correspond to the supplied drawing; all dimensional values are in millimetres.

Choose a conductor size to select its published order model and dimensional row.
Select any row to prepare an enquiry for that order model.
| Order selection | Published data | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Select | Order model | Conductor size | Article No. | A Cross Section | B Distance | C Width of Pin | D Length of Pin | E Modules | F Length | G Reference Current |
| 8 mm² | KP021208C | 8 | 17.8 | 5.5 | 11.5 | 12 | 210 | 50 A | ||
| 10 mm² | KP021210C | 10 | 17.8 | 5.5 | 11.5 | 12 | 210 | 63 A | ||
| 13 mm² | KP021213C | 13 | 17.8 | 5.5 | 11.5 | 12 | 210 | 70 A | ||
| 16 mm² | KP021216C | 16 | 17.8 | 5.5 | 11.5 | 12 | 210 | 80 A | ||
| 8 mm² | KP025408C | 8 | 17.8 | 5.5 | 11.5 | 54 | 1000 | 50 A | ||
| 10 mm² | KP025410C | 10 | 17.8 | 5.5 | 11.5 | 54 | 1000 | 63 A | ||
| 13 mm² | KP025413C | 13 | 17.8 | 5.5 | 11.5 | 54 | 1000 | 70 A | ||
| 16 mm² | KP025416C | 16 | 17.8 | 5.5 | 11.5 | 54 | 1000 | 80 A | ||
| 8 mm² | KP025608C | 8 | 17.8 | 5.5 | 11.5 | 56 | 1016 | 50 A | ||
| 10 mm² | KP025610C | 10 | 17.8 | 5.5 | 11.5 | 56 | 1016 | 63 A | ||
| 13 mm² | KP025613C | 13 | 17.8 | 5.5 | 11.5 | 56 | 1016 | 70 A | ||
| 16 mm² | KP025616C | 16 | 17.8 | 5.5 | 11.5 | 56 | 1016 | 80 A | ||
| 25 mm² | KP025425C | 25 | 17.8 | 6 | 11.5 | 54 | 1000 | 100 A | ||
Published dimensions are shown in millimetres unless another unit is displayed. Include the application, quantity and installation requirements in your enquiry.
Select the required conductor size above, then send the chosen order model with your quantity and application details.
Organized two-phase feed connections for compatible modular protective devices using M5.5 contacts.
Structured two-phase distribution where the 17.8 mm device distance and M5.5 pin geometry are required.
Repeat panel builds selected by Article No., cross-section, module count and finished length.
Use the published model table and dimension drawing for initial selection, then request controlled documentation with your enquiry.
The supplied drawing shows a repeating L1 and L2/N sequence across the two-phase pin busbar.
The Article No., conductor cross-section, module count, finished length, pin width for the 25 mm² option and reference current vary by row.