GV2 Motor Breaker Comb Busbar: Pitch Sizing, Current Limits, and Wiring Guide

GV2 Motor Breaker Comb Busbar: Pitch Sizing, Current Limits, and Wiring Guide
На этой странице

To specify a GV2-footprint motor breaker comb busbar without terminal misalignment, match the 3-pole tap-off pitch directly to your side-mounted accessories—45 mm for bare adjacent 3-pole manual motor starters, 54 mm when one 9 mm side auxiliary contact block sits between breakers, or 63 mm when an 18 mm side release or dual-auxiliary block occupies the gap—and keep grouped motor load within the busbar’s rated thermal current (typically 63 A).

This engineering guide addresses 3-phase grouped manual motor protection circuit breakers (MPCBs) built to IEC 60947-4-1 and IEC 60947-2 inside IEC 61439-1 control panels alongside North American UL 508A and UL 60947-4-1 industrial control panel group-motor wiring rules. Exact terminal torque, screw head clearance, and short-circuit ratings always remain governed by the installed motor breaker and busbar manufacturer drawings.

How 45 mm, 54 mm, and 63 mm GV2 Comb Busbar Pitches Map to Side Accessories

Unlike continuous 17.8 mm or 18 mm miniature circuit breaker (MCB) comb busbars, a GV2-footprint comb busbar groups stamped copper fork teeth into discrete 3-pole clusters (L1, L2, L3) separated by insulated skip-gaps. Choosing the wrong skip-gap pitch prevents the copper forks from entering adjacent motor breaker terminals whenever side-mounted status or trip blocks widen the row.

Because every GV2-footprint manual motor starter has a nominal 45 mm 3-pole body width, adding side-mounted blocks increases center-to-center spacing in exact 9 mm increments. (Standard 17.8 mm vs 18 mm lighting-breaker spacing follows different cumulative rules covered in our руководство по шагу установки автоматических выключателей.)

GV2 Tap-Off Pitch Side Accessory Width Between Breakers Typical Panel Configuration Standard Tap-Off Counts Ordering / Fit Boundary
45 mm pitch 0 mm (front-mount auxiliary only, or no side blocks) Bare 3-pole GV2 motor breakers clipped tight side-by-side on a 35 mm DIN rail 2, 3, 4, or 5 taps (6 to 15 poles) Reject if any 9 mm side-mount fault/status block is added later
54 mm pitch 9 mm (one side-mount auxiliary contact block per breaker) PLC-monitored motor groups using 1 × 9 mm side-mount NO/NC or fault-signaling block 2, 3, 4, or 5 taps Requires uniform 9 mm spacing between every consecutive breaker on the bar
63 mm pitch 18 mm (undervoltage release, shunt trip, or two 9 mm blocks) Safety-interlocked machinery panels using 18 mm side-mount trip coils 2, 3, or 4 taps Never mix 45 mm and 63 mm gaps on one standard fixed-pitch comb bar
Mixed / custom pitch Variable (e.g. one 18 mm release on Breaker 1, bare Breakers 2–4) Repeatable OEM machine panels with asymmetric side-block layouts Drawing-controlled custom tap count Specify a drawing-led KASEEY customized GV2 comb busbar rather than bending copper forks

Always finalize every side-mounted auxiliary contact, fault-signaling block, and undervoltage release on the panel CAD layout before locking a 45 mm, 54 mm, or 63 mm comb busbar pitch; adding a single 9 mm side block after procurement renders a 45 mm comb bar physically unusable across that gap.

Real KASEEY 5-tap GV2 3-phase fork comb busbar showing grouped 3-pole bare copper fork clusters, insulated skip-gap pitch zones, 3-layer laminated copper channel, and extruded white PVC spine
Real KASEEY 5-tap GV2-footprint 3-phase comb busbar illustrating grouped 3-pole bare copper fork clusters, insulated skip-gap pitch spacing, and the 3-layer laminated PVC insulation channel.

Sizing Feeder Current and End-Feed vs Center-Feed on a 63 A GV2 Comb Busbar

Standard GV2-footprint 3-phase comb busbars typically carry a 63 A free-air thermal current rating (Ith) across the copper spine. In motor panels where multiple pumps, fans, or conveyors run simultaneously inside 40°C to 55°C enclosures, total grouped motor full-load current (FLC) and feed-point placement determine whether one comb busbar can safely feed the row.

Moving the incoming main feeder from one end of the comb busbar to the center tap splits supply current into two parallel copper paths (left branch and right branch), reducing localized heating at the incoming terminal. For general continuous current-split physics across standard comb bars, see our руководстве по номинальным токам для конца питания и центра питания.

Grouped 3-Phase Motor Row Example Sum of Continuous Motor FLC Feed-In Entry Point Max Copper Spine Current Sizing Verdict (63 A Rated GV2 Bar)
3 motors: 8 A + 10 A + 12 A 30 A End-feed at Tap 1 via dedicated feed-in block 30 A Pass — ample thermal margin even at 50°C enclosure ambient
4 motors: 12 A + 14 A + 16 A + 18 A 60 A End-feed at Tap 1 60 A Marginal — zero derating headroom; relocate incoming feed to center tap
4 motors: 12 A + 14 A + 16 A + 18 A 60 A Center-feed between Tap 2 and Tap 3 26 A left / 34 A right Pass — balanced parallel current paths keep spine heating well below 63 A
5 motors: 16 A × 5 continuous 80 A Any single feed point on a 63 A bar 80 A total Reject single 63 A bar — split into two independently fed comb groups or upgrade feeder architecture

Whenever summed continuous motor full-load current approaches 80% of the comb busbar’s 63 A free-air rating inside a closed control cabinet, center-feed the busbar using a properly rated feed-in terminal block or split the motor row into two separately fed comb busbar groups.

Technical diagram comparing 45 mm, 54 mm with 9 mm auxiliary block, and 63 mm with 18 mm side release GV2 comb busbar pitches alongside end-feed versus center-feed current split
GV2-footprint tap-off pitch geometry (45 mm bare vs 54 mm + 9 mm auxiliary vs 63 mm + 18 mm side block) and end-feed versus center-feed current distribution across grouped 3-phase motor starters.

IEC 60947-4-1 and UL 508A Wiring Boundaries for Grouped Motor Starters

Manual motor protection circuit breakers built to IEC 60947-4-1 and IEC 60947-2 combine thermal overload and magnetic short-circuit protection, yet a comb busbar linking their line-side terminals still depends on upstream short-circuit protection and touch-safe insulation. In North American UL 508A industrial control panels, group-motor feeder busbars face strict feeder clearance, Short-Circuit Current Rating (SCCR), and UL listing rules.

Compliance Dimension IEC 60947-4-1 / IEC 61439-1 Control Panels North American UL 508A / UL 60947-4-1 Panels Panel Builder Verification Action
Upstream short-circuit coordination Conditional short-circuit current (Icc) verified with upstream gG backup fuse or current-limiting MCCB (see IEC 61439 comb busbar short-circuit ratings) Upstream branch/feeder SCPD must match the group-motor installation SCCR table and UL listing Document exact upstream fuse/MCCB model and prospective fault current (kA)
Line-side clearance and creepage Rated insulation voltage (Ui, typically 690 V AC) maintained by extruded 3-layer PVC/PA66 channel Feeder circuit spacing (typically 1 in / 25.4 mm through air and 2 in / 50.8 mm over surface unless UL-listed as a recognized feeder busbar) Confirm UL listing or Type E / group-motor busbar approval before North American export
Incoming main cable entry Dedicated top-entry feed-in terminal block or TB25/TB50 busbar feed-in connector sized for main wire gauge UL-listed feeder terminal block matched to the comb busbar tongue and copper conductor range (AWG) Never jam oversized stranded main cables alongside a fork tongue inside a single screw clamp
Unused 3-pole tap protection Mandatory IP20 finger-safe snap-on insulating cover over any empty 3-pole fork cluster Live exposed feeder forks prohibited inside operator-accessible panel doors Fit insulating protective covers over every unpopulated tap before energizing

Never treat an IEC-only 63 A GV2 comb busbar as automatically compliant for a UL 508A group-motor feeder circuit; verify destination-market listing documentation and feeder spacing requirements at the schematic stage.

De-Energized GV2 Comb Busbar Wiring and Torque Verification Steps

Installing a 3-phase fork comb busbar across grouped manual motor starters requires a strict de-energized sequence so every fork tongue seats squarely under its terminal clamping plate without bending the 3-layer laminated spine. (For general modular comb busbar installation fundamentals, refer to our comb busbar installation guide.)

  1. Isolate and lock out upstream power: Prove zero voltage across L1, L2, and L3 before handling line-side terminals or opening motor starter rows.
  2. Pre-assemble all side-mounted blocks on the DIN rail first: Clip every 9 mm auxiliary contact block and 18 mm trip coil onto its host GV2 breaker and seat all latches flush on the 35 mm DIN rail before introducing the comb busbar.
  3. Dry-fit the fork clusters with terminal screws backed out: Slide every 3-pole fork cluster smoothly under the moving clamp plates (never behind the clamp jaw). Any binding across Tap 3 to Tap 5 indicates a pitch mismatch (such as a 45 mm bar forced across a 9 mm auxiliary gap).
  4. Land the incoming feeder block and torque in sequence: Seat the dedicated incoming feed-in terminal block cleanly, then torque every line-side terminal screw to the motor breaker datasheet value (typically 1.7 to 2.5 N·m depending on frame) using a calibrated torque screwdriver.
  5. Seal unused taps and verify phase continuity: Snap matched 3-pole GV2 tap shrouds (or pitch-verified KASEEY protective covers where spacing matches) over any spare forks, then verify phase-to-phase insulation resistance before re-energizing.

Specifying Drawing-Led Custom GV2 Comb Busbars for OEM Production

Factory-sealed GV2 comb busbars are molded with closed insulated ends and fixed 3-pole fork clusters, so field cutting destroys inter-phase creepage distance and is strictly prohibited. When machine builders need non-standard tap counts, asymmetric pitch skips, tin-plated copper, or private-label marking, drawing-led OEM manufacturing eliminates unsafe field workarounds.

Before requesting a quotation for KASEEY customized GV2 comb busbars или custom busbar OEM tooling, prepare six concrete inputs (also summarized in our руководстве по расчету стоимости заказных соединительных шин): mating motor breaker terminal drawing, exact tap count (2 to 5+ taps), center-to-center pitch pattern (45 mm, 54 mm, 63 mm, or mixed), required thermal current rating and copper cross-section (mm²), surface finish (bare vs tin-plated copper), and destination market (IEC vs UL 508A) with estimated annual volume. Share your drawing package via KASEEY Contact or [email protected] for a dimensional and sample fit review.

Часто задаваемые вопросы

Can you cut a 5-tap GV2 comb busbar down to 3 taps in the field?

No. Unlike open-ended 1-meter cuttable MCB comb busbars, 3-phase GV2 motor breaker comb busbars are factory-molded closed assemblies with sealed end insulation designed for 690 V AC inter-phase creepage. Cutting a GV2 comb busbar exposes all three laminated copper phase strips at the cut face and voids IP20 touch protection and dielectric clearance—order the exact tap count (2, 3, 4, or 5 taps) or cap an unused tap with a matched insulating shroud.

Why cannot a standard 18 mm 3-phase MCB comb busbar fit GV2 motor breakers?

A standard 3-phase MCB comb busbar places phase teeth continuously every 17.8 mm or 18 mm (54 mm per 3-pole breaker), whereas a GV2-footprint manual motor starter packs all three phase terminals inside a 45 mm body (roughly 14.5 to 15 mm internal terminal spacing) with wider gaps between adjacent units. Attempting to force an 18 mm MCB busbar onto GV2 terminals misaligns every pole immediately.

What happens if one 3-pole tap on a GV2 comb busbar is left unused for future expansion?

Leaving an energized 3-pole fork cluster exposed violates IP20 finger-safe touch protection and creates a direct phase-to-phase short-circuit hazard if a dropped tool or loose ferrule bridges L1-L2-L3 during cabinet maintenance. Always snap a dedicated insulating protective cover over every unpopulated 3-pole tap before energizing the motor control panel.