{"id":4978,"date":"2026-11-23T15:55:20","date_gmt":"2026-11-23T15:55:20","guid":{"rendered":"https:\/\/kaseey.com\/?wpr2_import=fe7f1d7be5c322bb5c23fdd80f0dc66e584a3f6ed8ca8cb2d366cd31f599ae9d"},"modified":"2026-11-23T16:00:39","modified_gmt":"2026-11-23T16:00:39","slug":"comb-busbar-short-circuit-ratings-icw-ipk-iec-61439","status":"publish","type":"post","link":"https:\/\/kaseey.com\/de\/comb-busbar-short-circuit-ratings-icw-ipk-iec-61439\/","title":{"rendered":"Comb Busbar Short-Circuit Ratings (Icw &#038; Ipk): IEC 61439 Verification Guide"},"content":{"rendered":"<p>Under <a href=\"https:\/\/webstore.iec.ch\/\" target=\"_blank\" rel=\"noopener\">IEC 61439-1:2020 and IEC 61439-3:2024<\/a>, modular comb busbars inside low-voltage distribution boards (DBOs) are specified primarily by their rated conditional short-circuit current (Icc) coordinated with a current-limiting upstream protective device rather than a standalone 1-second short-time withstand rating (Icw). Assemblies whose prospective fault current does not exceed 10 kA r.m.s.\u2014or whose upstream current-limiting device caps peak cut-off current at \u2264 17 kA\u2014qualify for verification exemption under IEC 61439-1 Clause 10.11.2.<\/p>\n<p>This engineering guide defines short-circuit withstand boundaries for IEC 61439-3 modular distribution boards (outgoing circuits \u2264 125 A, assembly rating \u2264 250 A) and contrasts them with North American <a href=\"https:\/\/ulse.org\/\" target=\"_blank\" rel=\"noopener\">UL 508A and UL 489<\/a> Short-Circuit Current Rating (SCCR) rules. Continuous steady-state current split and end-feed versus center-feed sizing remain separate thermal criteria covered in our <a href=\"https:\/\/kaseey.com\/de\/comb-busbar-current-ratings-end-feed-centre-feed\/\">comb busbar end-feed vs center-feed ampacity guide<\/a>.<\/p>\n<h2>How Icw, Ipk, and Conditional Icc Differ on Comb Busbar Datasheets<\/h2>\n<p>Short-circuit ratings on a busbar specification measure two distinct physical stresses\u2014adiabatic thermal heating over fault clearing time (Icw) and instantaneous first-loop electrodynamic force (Ipk)\u2014alongside the system-level protected fault rating (Icc) achieved when an upstream fuse or breaker truncates the fault waveform. Confusing continuous load current (In) or conditional Icc with standalone Icw leads to underspecified main distribution boards.<\/p>\n<table>\n<thead>\n<tr>\n<th>Rating Symbol<\/th>\n<th>Full IEC 61439-1 Term<\/th>\n<th>Physical Stress Measured<\/th>\n<th>Typical Relevance to Modular Comb Busbars<\/th>\n<th>Governing Mathematical \/ Coordination Rule<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Icw<\/td>\n<td>Rated short-time withstand current (kA r.m.s., e.g. 0.3 s or 1 s)<\/td>\n<td>Adiabatic copper heating (I\u00b2t) and structural endurance without upstream clearing<\/td>\n<td>Rarely used alone for 8\u201325 mm\u00b2 comb busbars; primary metric for heavy solid copper busbars<\/td>\n<td>Thermal stress scales with Icw\u00b2 \u00d7 t; thin stamped pins melt quickly if held for a full 1 s fault<\/td>\n<\/tr>\n<tr>\n<td>Ipk<\/td>\n<td>Rated peak withstand current (kA peak)<\/td>\n<td>Maximum instantaneous electrodynamic repulsion\/pinch force during the first asymmetric current half-cycle<\/td>\n<td>Governs whether laminated phase bars spread apart, crack PVC phase barriers, or twist terminal clamps<\/td>\n<td>Ipk = n \u00d7 Icw, where factor n rises from 1.5 (\u2264 5 kA) to 1.7 (5\u201310 kA), 2.0 (10\u201320 kA), and 2.1 (20\u201350 kA)<\/td>\n<\/tr>\n<tr>\n<td>Icc<\/td>\n<td>Rated conditional short-circuit current (kA r.m.s.)<\/td>\n<td>Prospective network fault current survived only when protected by a specified upstream current-limiting device<\/td>\n<td>Primary short-circuit rating for IEC 61439-3 comb busbars paired with gG backup fuses or current-limiting MCCBs<\/td>\n<td>Valid only when the installed upstream fuse\/breaker type, ampere rating, and let-through I\u00b2t match the tested coordination<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Never substitute a conditional Icc figure for an unbacked Icw requirement; if your panel specification demands a standalone 1-second Icw rating without upstream current limitation, a standard modular comb busbar is structurally unsuitable and must be replaced by a braced pan assembly or solid copper busbar system.<\/p>\n<figure class=\"wp-block-image\">\n<img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/kaseey.com\/wp-content\/uploads\/2026\/11\/comb-busbar-short-circuit-ratings-icw-ipk-iec-61439-hardware-zones-a3d0bd546f4a8cecd55372be0a633a6bef66bf202f4cc372a7a78153c1f5f846.webp\" width=\"1920\" height=\"1080\" alt=\"Real KASEEY fork-type M6 and pin-type P-1L copper comb busbars showing the four physical short-circuit stress zones: laminated copper spine, extruded PVC phase barrier, stamped fork root, and pin tooth contact\"><figcaption>Key short-circuit stress zones on modular KASEEY copper comb busbars: laminated copper spine cross-section, extruded inter-phase PVC barrier wall, stamped fork root, and pin tooth contact land.<\/figcaption><\/figure>\n<h2>Electrodynamic Peak Force (Ipk) vs Adiabatic Heating (I\u00b2t) in Multi-Phase Comb Busbars<\/h2>\n<p>During a bolted phase-to-phase short circuit across a 2P, 3P, or 4P comb busbar, magnetic repulsion force between closely spaced laminated copper strips increases with the square of the peak current (Ipk\u00b2) and inversely with phase-to-phase centerline spacing. Simultaneously, fault energy (I\u00b2t) heats the narrow stamped copper tooth necks adiabatically within milliseconds before heat can conduct into the surrounding air.<\/p>\n<p>Because multi-phase comb busbars stack L1, L2, L3, and N copper strips separated by only millimeters of extruded PVC or PA66 insulation, three localized failure modes govern real-world fault endurance:<\/p>\n<ul>\n<li><strong>Inter-phase barrier splitting under Ipk peak force<\/strong>: Opposite fault currents flowing in adjacent laminated bars generate outward magnetic pressure that tries to blow the extruded plastic channel open. Any hairline crack or compromised cut end without properly seated <a href=\"https:\/\/kaseey.com\/de\/busbar-end-caps\/busbar-end-caps-ek1-4\">EK1-4 insulating end caps<\/a> turns mechanical spread into a phase-to-phase flashover.<\/li>\n<li><strong>Tooth-root necking and cantilever pull-out<\/strong>: Even when the main horizontal copper spine is 16 mm\u00b2 or 25 mm\u00b2, each individual pin or fork tooth is a smaller stamped cantilever beam anchored only by the mating MCB terminal screw. High Ipk torque can bend a loosely clamped tooth sideways or blow a half-seated pin out of its cage.<\/li>\n<li><strong>Adiabatic let-through melting (I\u00b2t) at the feed-in zone<\/strong>: The highest fault current density always concentrates between the incoming feed point and the faulted outgoing MCB. Upstream current-limiting gG fuses or fast-acting <a href=\"https:\/\/webstore.iec.ch\/\" target=\"_blank\" rel=\"noopener\">IEC 60898-1<\/a> current-limiting breakers cut off the fault before the first natural peak, slashing both Ipk force and I\u00b2t thermal stress to a fraction of the prospective bolted value.<\/li>\n<\/ul>\n<figure class=\"wp-block-image\">\n<img loading=\"lazy\" decoding=\"async\" src=\"https:\/\/kaseey.com\/wp-content\/uploads\/2026\/11\/comb-busbar-short-circuit-ratings-icw-ipk-iec-61439-cad-forces.webp\" width=\"1920\" height=\"1080\" alt=\"Isometric CAD cutaway of a 3-phase copper comb busbar clamped inside modular DIN-rail terminals showing Ipk electrodynamic repulsion between laminated phase bars and I\u00b2t adiabatic thermal concentration at the tooth root\"><figcaption>Isometric CAD cutaway illustrating how peak short-circuit current (Ipk) drives magnetic repulsion between laminated phase bars while let-through energy (I\u00b2t) concentrates thermal stress at the clamped tooth root.<\/figcaption><\/figure>\n<h2>IEC 61439-1 Clause 10.11.2 Verification Exemptions (10 kA and 17 kA Rules) vs UL 508A SCCR<\/h2>\n<p>IEC 61439-1:2020 Clause 10.11.2 exempts specific low-voltage assembly circuits from physical short-circuit testing or calculation whenever fault stress stays below two strict statutory ceilings: a rated Icw or Icc not exceeding 10 kA r.m.s., or an upstream current-limiting protective device whose maximum cut-off peak current does not exceed 17 kA at the assembly&#8217;s rated conditional short-circuit current.<\/p>\n<p>Panel builders exporting across European IEC and North American UL markets must apply completely separate verification frameworks because IEC conditional exemptions do not carry over into UL listing evaluations:<\/p>\n<table>\n<thead>\n<tr>\n<th>Verification Regime<\/th>\n<th>Governing Standard<\/th>\n<th>Exemption \/ Pass Boundary<\/th>\n<th>Mandatory Action Above Boundary<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>IEC Low Fault-Level Exemption<\/td>\n<td><a href=\"https:\/\/webstore.iec.ch\/\" target=\"_blank\" rel=\"noopener\">IEC 61439-1:2020<\/a> Clause 10.11.2 (a)<\/td>\n<td>Rated Icw or Icc \u2264 10 kA r.m.s. (corresponding peak \u2264 17 kA)<\/td>\n<td>Full design verification by short-circuit testing or comparison to a tested reference assembly<\/td>\n<\/tr>\n<tr>\n<td>IEC Current-Limiting Cut-Off Exemption<\/td>\n<td><a href=\"https:\/\/webstore.iec.ch\/\" target=\"_blank\" rel=\"noopener\">IEC 61439-1:2020<\/a> Clause 10.11.2 (b)<\/td>\n<td>Upstream current-limiting device limits let-through peak current to \u2264 17 kA at the panel&#8217;s prospective fault level<\/td>\n<td>Must document tested coordination between the exact upstream breaker\/fuse, comb busbar, and outgoing devices<\/td>\n<\/tr>\n<tr>\n<td>IEC Distribution Boards (DBOs)<\/td>\n<td><a href=\"https:\/\/webstore.iec.ch\/\" target=\"_blank\" rel=\"noopener\">IEC 61439-3:2024<\/a> (Inc \u2264 125 A, InA \u2264 250 A)<\/td>\n<td>Assembly verified as a complete system by the Original Manufacturer<\/td>\n<td>Substituting an unverified comb busbar or higher-rated backup fuse invalidates conditional Icc compliance<\/td>\n<\/tr>\n<tr>\n<td>North American Industrial Control Panels<\/td>\n<td><a href=\"https:\/\/ulse.org\/\" target=\"_blank\" rel=\"noopener\">UL 508A<\/a> (Supplement SB) &amp; <a href=\"https:\/\/ulse.org\/\" target=\"_blank\" rel=\"noopener\">UL 489<\/a><\/td>\n<td>Comb busbars must carry UL Listing\/Recognition for the specific branch-circuit device family and stated SCCR (kA)<\/td>\n<td>Assembly SCCR defaults to the lowest unmarked component rating (often 5 kA) unless listed feeder busbar combinations are documented<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Verify your destination market&#8217;s verification route before specifying hardware; for exact documentation distinctions between EU CE conformity declarations and North American UL component files, review our <a href=\"https:\/\/kaseey.com\/de\/mcb-busbar-ce-ul-documentation\/\">MCB busbar CE and UL documentation guide<\/a>.<\/p>\n<h2>Choosing Between Comb Busbars, Pan Assemblies, and Solid Copper Bars by Fault Level<\/h2>\n<p>Selecting the right busbar architecture requires matching both continuous row current (In) and prospective short-circuit fault level (kA) at the installation point. Upgrading comb busbars from 10 mm\u00b2 to 16 mm\u00b2 or 25 mm\u00b2 raises thermal I\u00b2t headroom, but high fault levels without fast upstream current limitation require braced pan assemblies or solid copper bars. See our <a href=\"https:\/\/kaseey.com\/de\/blog\/how-to-select-an-mcb-busbar\">MCB-Sammelschienen-Auswahlhilfe<\/a> for full row sizing.<\/p>\n<table>\n<thead>\n<tr>\n<th>Prospective Fault Context<\/th>\n<th>Upstream Protection Profile<\/th>\n<th>Suitable Busbar Architecture<\/th>\n<th>KASEEY Hardware Scope<\/th>\n<th>Critical Engineering Check<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Sub-distribution board (prospective fault \u2264 10 kA r.m.s., row \u2264 80 A)<\/td>\n<td>Standard IEC 60898-1 main breaker or gG backup fuse<\/td>\n<td>Standard modular pin-type or fork-type comb busbar (8\u201316 mm\u00b2)<\/td>\n<td><a href=\"https:\/\/kaseey.com\/de\/busbars\/pin-type-1-phase-busbars-p-1l\">Pin-type P-1L comb busbars<\/a> + <a href=\"https:\/\/kaseey.com\/de\/busbar-end-caps\/busbar-end-caps-ek1-4\">EK1-4 end caps<\/a><\/td>\n<td>Confirm Clause 10.11.2 exemption applies and torque all terminals to device datasheet<\/td>\n<\/tr>\n<tr>\n<td>Commercial DBO (prospective fault 10\u201325 kA, row up to 100 A)<\/td>\n<td>Current-limiting gG backup fuse or current-limiting MCCB capping cut-off peak \u2264 17 kA (or tested Icc coordination)<\/td>\n<td>Heavy-duty modular comb busbar (16\u201325 mm\u00b2) with verified conditional Icc coordination<\/td>\n<td><a href=\"https:\/\/kaseey.com\/de\/busbars\/fork-type-3-phase-busbars-m6\">Fork-type M6 comb busbars<\/a> (up to 25 mm\u00b2 \/ 100 A)<\/td>\n<td>Verify upstream fuse\/MCCB let-through curve matches the assembly&#8217;s documented Icc limit<\/td>\n<\/tr>\n<tr>\n<td>High-density commercial panelboard (125 A\u2013250 A main incomer, higher fault duty)<\/td>\n<td>Molded-case circuit breaker (MCCB) incomer feeding multi-way outgoing MCBs<\/td>\n<td>Factory-assembled pan assembly busbar interior with rigid insulated chassis<\/td>\n<td><a href=\"https:\/\/kaseey.com\/de\/pan-assembly-busbars\/pan-assembly-busbar\">Pan assembly busbars KP-125A \/ KP-250A<\/a><\/td>\n<td>Review connect-tab width, copper thickness, and assembly bracing in our <a href=\"https:\/\/kaseey.com\/de\/pan-assembly-busbar-ratings-explained\/\">pan assembly busbar ratings guide<\/a><\/td>\n<\/tr>\n<tr>\n<td>Main switchboard \/ high-fault feeder (&gt; 250 A or standalone 1 s Icw required)<\/td>\n<td>Selective delayed-trip MCCB or ACB requiring unbacked short-time withstand<\/td>\n<td>Solid rectangular copper busbars mounted on engineered high-strength insulators<\/td>\n<td><a href=\"https:\/\/kaseey.com\/de\/copper-bars\/copper-bar-kb-series\">KB series solid copper bars<\/a><\/td>\n<td>Size conductor cross-section and insulator support pitch for Ipk dynamic force; see <a href=\"https:\/\/kaseey.com\/de\/copper-busbar-current-capacity\/\">copper busbar current capacity<\/a><\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>Escalate from a modular comb busbar to a pan assembly or braced solid copper bar whenever selective delayed-trip upstream protection eliminates fast current limitation or whenever total assembly current exceeds 100 A continuous duty.<\/p>\n<h2>Short-Circuit Specification Checklist for Panel Builders and OEM RFQs<\/h2>\n<p>Requesting verified short-circuit coordination data early prevents costly redesigns during third-party IEC 61439 or UL 508A panel inspection. Before issuing a comb busbar or custom OEM busbar RFQ, assemble five concrete electrical inputs covering incoming fault level, upstream protection class, conductor cross-section, end-cap insulation, and target market standards.<\/p>\n<ol>\n<li><strong>Prospective fault current at incoming terminals (kA r.m.s.)<\/strong>: Distinguish between network prospective current (Icp) and the reduced let-through peak current behind your upstream main breaker or backup fuse.<\/li>\n<li><strong>Upstream protective device class and rating<\/strong>: Specify whether protection relies on a gG fuse (exact A rating), an IEC 60898-1 MCB, or a current-limiting MCCB, as this determines conditional Icc validity.<\/li>\n<li><strong>Target conductor cross-section and phase architecture<\/strong>: State required copper cross-section (10 mm\u00b2, 16 mm\u00b2, or 25 mm\u00b2), pole sequence (1P, 2P, 3P, 4P, or 3L+3N), and terminal interface (pin vs fork).<\/li>\n<li><strong>Cut-end and spare-way insulation requirements<\/strong>: Include matching end caps (EK1-4) and protective tooth covers so fault-induced ionization cannot track across exposed copper ends.<\/li>\n<li><strong>Destination market compliance route<\/strong>: Clarify whether the finished board is verified under IEC 61439-3, IEC 61439-1\/-2, or North American UL 508A \/ UL 67.<\/li>\n<\/ol>\n<p>If you are specifying modular comb busbars, pan assemblies, or custom OEM busbars for a verified distribution board program, share your prospective fault level, upstream protection type, pole sequence, cross-section (mm\u00b2), mating device drawings, destination market, and volume via <a href=\"https:\/\/kaseey.com\/de\/contact\">KASEEY Contact<\/a>, <a href=\"https:\/\/kaseey.com\/de\/solutions\/custom-busbar-oem\">Custom Busbar OEM<\/a>, or sales@kaseey.com for an engineering specification review.<\/p>\n<h2>H\u00e4ufig gestellte Fragen<\/h2>\n<h3>Does a 16 mm\u00b2 comb busbar automatically have a higher short-circuit rating than a 10 mm\u00b2 bar?<\/h3>\n<p>A 16 mm\u00b2 copper comb busbar holds roughly 2.56 times the adiabatic I\u00b2t thermal margin of a 10 mm\u00b2 bar of the same material, because adiabatic short-circuit capability scales with the square of cross-sectional area. However, its certified conditional Icc rating still depends on inter-phase insulation wall strength, tooth-root clamping security, and the tested upstream current-limiting device.<\/p>\n<h3>Why do comb busbars require an upstream backup fuse for a 25 kA Icc rating?<\/h3>\n<p>A lightweight modular comb busbar cannot survive a full 25 kA bolted fault for 0.3 to 1.0 second without melting or spreading its insulated phase layers. A properly sized upstream current-limiting gG fuse melts within milliseconds during the rising edge of the first half-cycle, cutting off both peak electrodynamic force (Ipk) and let-through thermal energy (I\u00b2t) to safe levels.<\/p>\n<h3>Can you use IEC 61439 Icc ratings to establish North American UL 508A SCCR?<\/h3>\n<p>No. IEC 61439-1 Clause 10.11.2 exemptions (10 kA r.m.s. and 17 kA peak cut-off) and IEC conditional Icc coordination tables are not accepted as proof of UL 508A Supplement SB Short-Circuit Current Rating. Panels built for North American inspection must use UL-listed or UL-recognized feeder busbars evaluated with their specific UL 489 branch-circuit devices.<\/p>\n<h2>Quellen<\/h2>\n<ul>\n<li><a href=\"https:\/\/webstore.iec.ch\/\" target=\"_blank\" rel=\"noopener\">IEC Webshop \u2014 IEC 61439-1:2020 und IEC 61439-3:2024<\/a> \u2014 International Electrotechnical Commission (IEC); official standards catalogue defining Icw, Ipk, and Icc short-circuit verification rules, Clause 10.11.2 verification exemptions (10 kA r.m.s. and 17 kA cut-off peak), and DBO ratings (Inc \u2264 125 A, InA \u2264 250 A).<\/li>\n<li><a href=\"https:\/\/webstore.iec.ch\/\" target=\"_blank\" rel=\"noopener\">IEC Webstore \u2014 IEC 60898-1:2015+AMD1:2019<\/a> \u2014 International Electrotechnical Commission (IEC); official standards catalogue for AC miniature circuit-breakers (MCBs) up to 125 A and 25 kA rated short-circuit capacity.<\/li>\n<li><a href=\"https:\/\/ulse.org\/\" target=\"_blank\" rel=\"noopener\">UL Standards &amp; Engagement \u2014 UL 489 and UL 508A<\/a> \u2014 UL Standards &amp; Engagement; official standards discovery portal covering molded-case circuit breakers (UL 489) and industrial control panels SCCR verification (UL 508A).<\/li>\n<li><a href=\"https:\/\/kaseey.com\/de\/busbars\/pin-type-1-phase-busbars-p-1l\">Stift-Phasenschienen 1 P-1L | KASEEY<\/a> \u2014 KASEEY; first-party specification documenting standard 8\u201316 mm\u00b2 comb busbar cross-sections and 50\u201380 A continuous ratings.<\/li>\n<li><a href=\"https:\/\/kaseey.com\/de\/busbars\/fork-type-3-phase-busbars-m6\">Gabel-Phasenschienen 3 M6 | KASEEY<\/a> \u2014 KASEEY; first-party specification documenting extended M6 fork-type comb busbar ratings up to 25 mm\u00b2 and 100 A.<\/li>\n<li><a href=\"https:\/\/kaseey.com\/de\/pan-assembly-busbars\/pan-assembly-busbar\">Sammelschienen f\u00fcr Schalttafelmontage KP-125A und KP-250A | KASEEY<\/a> \u2014 KASEEY; first-party specification for factory-assembled 125 A and 250 A pan assembly busbar interiors.<\/li>\n<li><a href=\"https:\/\/kaseey.com\/de\/copper-bars\/copper-bar-kb-series\">Kupferschiene KB Serie | KASEEY<\/a> \u2014 KASEEY; first-party product page for solid rectangular copper distribution busbars.<\/li>\n<li><a href=\"https:\/\/kaseey.com\/de\/busbar-end-caps\/busbar-end-caps-ek1-4\">Busbar End Caps EK1-4 | KASEEY<\/a> \u2014 KASEEY; first-party product page for insulating comb busbar end caps.<\/li>\n<\/ul>","protected":false},"excerpt":{"rendered":"<p>Under IEC 61439-1:2020 and IEC 61439-3:2024, modular comb busbars inside low-voltage distribution boards (DBOs) are specified primarily by their rated conditional short-circuit current (Icc) coordinated with a current-limiting upstream protective device rather than a standalone 1-second short-time withstand rating (Icw). Assemblies whose prospective fault current does not exceed 10 kA r.m.s.\u2014or whose upstream current-limiting device [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":4977,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[27],"tags":[],"class_list":["post-4978","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-busbars"],"_links":{"self":[{"href":"https:\/\/kaseey.com\/de\/wp-json\/wp\/v2\/posts\/4978","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/kaseey.com\/de\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/kaseey.com\/de\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/kaseey.com\/de\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/kaseey.com\/de\/wp-json\/wp\/v2\/comments?post=4978"}],"version-history":[{"count":2,"href":"https:\/\/kaseey.com\/de\/wp-json\/wp\/v2\/posts\/4978\/revisions"}],"predecessor-version":[{"id":4981,"href":"https:\/\/kaseey.com\/de\/wp-json\/wp\/v2\/posts\/4978\/revisions\/4981"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/kaseey.com\/de\/wp-json\/wp\/v2\/media\/4977"}],"wp:attachment":[{"href":"https:\/\/kaseey.com\/de\/wp-json\/wp\/v2\/media?parent=4978"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/kaseey.com\/de\/wp-json\/wp\/v2\/categories?post=4978"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/kaseey.com\/de\/wp-json\/wp\/v2\/tags?post=4978"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}